LNDAM1
Thermal Adjustable Magnetic adjustable Circuit Breakers (TAMA) |
||||||||||||||||
Model | DAM1-250 | DAM1-630(400) | DAM3-1000 | DAM3-1600 | ||||||||||||
Breaking Capacity Code |
N | S | H | G | N | S | H | G | N | S | H | S | H | G | ||
Rated Current of Frame size- Inm (A) |
250A | 400A | 800A | 1600A | ||||||||||||
Rated Current-In (40,50 or 55℃) (A) |
125 - 160(180) - 200(225) - 250 - 320A |
250 - 315 (350)- 400 - 500 - 630A |
400 - 500 - 630 (700)- 800-1000A |
1000 - 1250 - 1600A |
||||||||||||
Rated İnsulation Voltage -Ui(a.c.) 50-60Hz (V) |
1000V | 1000V | 1000V | 1000V | ||||||||||||
Rated operation Voltage -Ue(a.c.) 50-60Hz (V) |
400/415V | 400/415V | 400/415V | 400V | ||||||||||||
Number of Pole | 3P | 3P /4P | 3P | 3P | ||||||||||||
Rated ultimate short Circuit breaking Capacity kA Icu AC400V /50Hz O- CO (KA) |
35 | 50 | 65 | 85 | 35 | 50 | 70 | 85 | 36 | 55 | 70 | 55 | 70 | 85 | ||
Rated service short Circuit breaking Capacity kA Ics AC400V /50Hz O- CO-CO (KA) |
26.25 | 37.5 | 48.75 | 51 | 26.25 | 37.5 | 52.5 | 52.5 | 36 | 36 | 50 | 36 | 50 | 55 | ||
Rated short- circuit breaking capacity Icm (peak)/cos ф AC400V/50HZ O-CO (KA) |
77/ 0.25 |
114/ 0.25 |
143/ 0.2 |
178/ 0.2 |
70/ 0.25 |
110/ 0.25 |
154/ 0.2 |
187/ 0.2 |
77/ 0.25 |
100/ 0.25 |
154/ 0.2 |
105/ 0.25 |
143/ 0.2 |
220/ 0.2 |
||
Rated impulse withstand Voltage - Uimp (V) |
8000 | 8000 | 8000 | 8000 | ||||||||||||
Dielectric Propery (V) |
3000 | 3000 | 3000 | 3000 | ||||||||||||
lonization distance (mm) |
≤30/0※ | ≤60/0※ | ≤80/0※ | ≤80/0※ | ||||||||||||
Endurance |
Total Cycles |
8000 | 5000 | 5000 | 3000 | |||||||||||
Electrical Life |
1000 | 1000 | 1000 | 500 | ||||||||||||
Mechanical Life |
7000 | 4000 | 4000 | 2500 | ||||||||||||
Over Current trip | Thermal release adjustable |
Min:0,7In -Max:1In |
Min:0,7In -Max:1In |
Min:0,7In -Max:1In |
Min:0,7In -Max:1In |
|||||||||||
Magnetic release adjustable | 5In-10In | 5In-10In | 5In-10In | 5In-10In | ||||||||||||
Category (EN 60947- 2/IEC 60947-2) |
Main circuit |
A/B | A/B | A/B | A/B | |||||||||||
Auxiliary circuit |
AC-15 | AC-15 | AC-15 | AC-15 | ||||||||||||
Under Voltage Release |
√ | √ | √ | √ | ||||||||||||
Shunt Release | √ | √ | √ | √ | ||||||||||||
Auxiliary Contact | √ | √ | √ | √ | ||||||||||||
Alarm Contact | √ | √ | √ | √ | ||||||||||||
Auxiliary Contact and Alarm Contact |
√ | √ | √ | √ | ||||||||||||
Handle Operation Mechanism | √ | √ | √ | √ | ||||||||||||
Electrical Operastion Mechanism | √ | √ | √ | √ | ||||||||||||
DIN clips | - | - | - | - | ||||||||||||
Terminal cover | √ | √ | √ | √ | ||||||||||||
Phase seperator | √ | √ | √ | √ | ||||||||||||
Extention Handle | √ | √ | √ | √ | ||||||||||||
W (mm) |
3P | 105 | 140 | 210 | 210 | |||||||||||
4P | - | 184 | - | - | ||||||||||||
L (mm) |
3P | 212.5 | 254 | 268 | 328 | |||||||||||
4P | - | 254 | - | - | ||||||||||||
H (mm) |
3P | 103.5 | 103.5 | 167 | 196 | |||||||||||
4P | - | 103.5 | - | - |