LNPCA
TUV 2 PfG 1169 PV1-F1000
DC (Twin Core)
Solar Cable
For Australian market
DC (Twin Core)
Solar Cable
For Australian market
● Conductor: Soft tinned annealed copper according to VDE 0296/IEC 60228, class 5
● Insulation: XLPE, halogen free, E-Beam cross-linked compounds
● Jacket: XLPE, flame retardant, halogen free, E-beam cross-linked compounds, UV and ozone resistant,
black/white marking
● Rated Voltage: U /U=0.6/1KV AC 1000/1800V DC For DC installation
● Test Voltage: 6500V/5min
● Fixed setting: >4 x Φ
● Moves on occasion: >5 x Φ
● Fireproof performance: IEC 60332-1, IEC 60332-3-24
● Smoke emission: IEC 61034, EN 61034-2
● Low fire load: DIN 51900
● Approval: TUV
● Applied standard: 2 PfG 1169/08.2007
● Operation temperature: -40°C~ +120°C
● Ambient temperature: -40°C ~ +90°C
● Maximum short circuit temperature: 280°C, +536°F, 5s
Conductor | Insulation | Outer Jacket | Construction | Outer Dia. mm |
Coductor resistance (20℃) |
Current | |
n*mm | Color | Color | N/mm | A | B | max.mΩ/m | A |
2*4.0 | Black/Red | Black | 56/0.285±0.005 | 5.0±0.1 | 10.10±0.2 | 5.09 | 55.0 |