LNL11-40
2 Modules 1P+N RCBO
Standards | IEC/EN 61009-1,AS/NZS 61009.1 | |
Type | Electro-magnetic | |
Residual current characteristics | A, AC | |
Pole No. | 1P+N | |
Rated current | 6,10,16,20,25,32,40A | |
Rated voltage | 110/230/240V AC | |
Rated frequency | 50/60Hz | |
Tripping curve | B: Non-inductive or Micro-inductive | |
C: Protecting normal specification load | ||
and distribution cable | ||
Rated residual making and breaking capacity (I△m) | 500A for IEC,3000A for EN | |
Rated making and breaking capacity(Icn) | 6000A,10000A | |
Rated residual operating current (I △ n) | 30,100,300mA | |
Rated residual non operating current (l △ no) | 0.5I△n | |
Electro-mechanical endurance | 4000 | |
Maximum connecting fuse | 100A gL(>10KA) | |
Connection terminal | Screw terminal | |
Connection capacity | Pillar terminal with clamp | |
Leakage operation time | Rigid conductor 25mm² | |
Residual current off-time | Min time delay 10ms | |
0.5I△n | t=∞ | |
1 I△n | t≤0.3s | |
2I△n | t≤0.15s | |
5I△n | t≤0.04s |