LNA18-MR
Accessories for LNM18 & LNL18 series of Circuit Breakers
Accessory name | Rated current (A) | Number of contacts per group |
Wiring diagram | ||
AC: 380V | AC: 220V | DC: 1 1 0V | |||
Auxiliary contact OF | 3 | 6 | 1 | Normally open Normally closed |
|
Alarm contact SD | 3 | 6 | 1 | Normally open Normally closed |
Accessory name | Rated insulation voltage Ui |
Rated control power supply voltage Us |
Trip power consumption(W or VA) |
Pull-in voltage | Wiring diagram |
MX Shunt release | 415V | AC/DC : 220~380V 110~220V |
240 | ( 0 .7~1 .1 ) Us |
|
AC/DC : 24~48V | 120 | ||||
Shunt release + auxiliary contact MX + OF |
415V | AC/DC : 220~380V 110~220V |
240 | ( 0 .7~1 .1 ) Us |
|
AC/DC : 24~48V | 120 | ||||
Overvoltage, undervoltage release MV + MN |
415V | AC : 220~240V | 120 | ( 0 .7~1 .1 ) Us |